Develop ladder logic that will cycle the cylinder in and out repeatedly, and watch for failure.
plc timers -9.32
9.10 PRACTICE PROBLEM SOLUTIONS
1. edge triggered means the event when a logic signal goes from false to true (positive edge) or from true to false (negative edge).
2. no, but they are essential for retentive timers, and very important for counters.
3. these are limited by the 16 bit number for a range of -32768 to +32767
4. the un underflow bit. This may result in a fault in some PLCs.
5. first pass
motor stop
start motor
6.
start stop
motor
motor
plc timers -9.33
7.
RTF
A Timer T4:0 Time Base 0.01 (DN)
Preset 350
Accum. 0 (EN)
plc timers -9.34
8.
RTO
A Timer T4:0 (DN)
Time Base 1.0 Preset 10 (EN)
Accum. 1
TOF
A Timer T4:1 Time Base .01 (EN)
Preset 50
Accum. 0 (DN)
T4:1 EN
T4:1 TT T4:1 DN
T4:1 Accum. 0 15 45 150 200
A
plc timers -9.36
12.
I/1
O/01
TON
B3/0 T4:0 delay 15 sec
T4:0/DN
13.
plc timers -9.37
14.
C5:0/DN
plc timers -9.38
15.
C5:1DN
C5:0 C5:1
plc timers -9.39
16.
TON Timer T4:0 Base 0.01 Preset 25
TON Timer T4:1 Base 0.01 Preset 25
on
plc timers -9.40
17.
plc timers -9.41
18.
light
B
plc timers -9.42
1.
2.
3. BACK | NEXT Easy Access To All Pages 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140
|